SFS or Blockwork for External Infill Walls

A fair comparison of light steel infill and blockwork prices the same build-up on both sides and checks movement and wind at the structure.

The steelconstruction.info "Infill walling" page, which promotes steel construction, claims time savings of over two weeks per floor for light steel infill compared with blockwork. That is an industry claim, so test it against the programme for the scheme in question.

The same page and the FIS through-wall guide (launched 10 October 2022) give a useful checklist of what to compare.

Programme

The page says light steel gives a weather-tight envelope sooner so other trades can start earlier, and describes blockwork as messy and time-consuming. Compare like with like by including design and procurement before the first stud is fixed, as well as installation per floor.

The page also says the site-assembled approach suits renovation, where tolerances in the original construction have to be accommodated. Its top track lets the studs slide and adjust in height.

Weight on the structure

The page gives a typical line load of 2 kN/m for a light steel wall with lightweight cladding. Ask the structural engineer for the line load of the blockwork alternative rather than relying on a comparison from either side.

Movement at the head

The page says concrete frames can shorten by 2 to 3 mm per floor over time, which is why a sliding top track is needed. It gives movement allowances at the top of the wall:

  • Steel structures: beam span/500 or 10 mm, whichever is greater.
  • Concrete structures: beam span/300 or 20 mm, whichever is greater.

The page does not cover the head detail for blockwork, so ask for it on that side of the comparison.

Wind and openings

Infill walls are considered non-load bearing but resist wind loads. The page cites BS EN 1991-1-4 for wind actions and says light steel walls can resist up to 2 kN/m2. It says blockwork needs strengthening posts beside openings because it is not strong enough for the high local wind loads there.

The page says large windows up to 3 m high and 5 m wide can be formed using multiple C sections. For brick cladding on taller buildings, it says the brick should be supported by the frame using stainless steel angles.

Fire

Steel is non-combustible. The page says two layers of Type F plasterboard give at least 60 minutes for an infill wall, and more layers can reach 120 minutes. It gives no blockwork figures, and any rating should come from a tested system.

Thermal and acoustic

The page says about 100 mm of external insulation is generally needed for a U-value of 0.2 W/m2K. Its acoustic table gives these Rw values:

  • Solid lightweight blockwork, 100 mm block and plaster: about 43 dB.
  • Basic light steel with external insulation: about 45 dB.
  • Light steel with a brickwork outer leaf: about 60 dB.

Scope definition

FIS says its guide gives a standard definition of "through-wall". It sets out three build-ups: inner plasterboard to external sheathing board; the same plus external wall insulation; and the same plus a facade system.

Quotes labelled "SFS" can therefore include different layers. FIS also says the integration and interface into the building structure should be addressed early in design.

A fair comparison prices the same build-up on each side, from inner lining to external finish.

Common questions

Is an SFS infill wall load bearing?

The steelconstruction.info page says infill walls are considered non-load bearing but they resist wind loads.

Where can the FIS guide be found?

The FIS through-wall guide is free to FIS members. Non-members can request a copy from FIS.

Which wind standard does the page cite?

It cites BS EN 1991-1-4 and, for older calculations, BS 6399-2. Confirm the design basis with the SFS designer.