Why Partitions Fail Part E Sound Tests

Most failures trace to gaps, rigid links and missing absorbent material at junctions, all of which Approved Document E and SCI guidance describe.

Approved Document E sets a minimum airborne sound insulation of 45 dB DnT,w + Ctr for a purpose built separating wall between dwellings, and 43 dB for a wall formed by material change of use. Pre-completion testing checks the figure on site, and one individual test below the value fails the whole set (paragraph 1.32).

The edition in force for England is the 2003 edition with amendments to 2015, reprinted in October 2015, as at November 2026.

The target and the test

The performance standards also include impact sound for floors. Purpose built floors and stairs need a minimum of 45 dB airborne and a maximum of 62 dB L'nT,w impact. For rooms for residential purposes, the purpose built wall value is 43 dB.

Building control bodies should stipulate at least one set of tests for every ten dwelling-houses, flats or rooms for residential purposes in a group or sub-group (paragraph 1.30). Testing should be more frequent at the start of a series of completions.

Gaps and missing material

The guidance returns to air paths repeatedly:

  • Unsealed joints. The Approved Document says wall lining joints should be sealed with tape or caulked with sealant, and so should the junction between ceiling and wall linings.
  • Gaps at junctions. The SCI says any gaps should be sealed with acoustic sealant, including where wall boards meet the floor deck.
  • Back-to-back sockets and chasing. The framed wall guidance says do not locate sockets back to back, recommends a minimum edge to edge stagger of 150 mm, and says do not chase plasterboard. That guidance is written for timber frames.
  • Missing absorbent material. The SCI lists missing or insufficient mineral wool in stud voids at floor zones as a fault. For steel framed walls, the Approved Document says to seek advice from the manufacturer.

For timber framed separating walls (type 4.1), the Approved Document specifies unfaced mineral wool of at least 10 kg/m3 density, at least 25 mm thick if suspended in the cavity or 50 mm if fixed to one frame. Each plasterboard sheet must have a minimum mass of 10 kg/m2, with staggered joints between layers.

Bridges and flanking paths

Sound travels around a wall as well as through it. Faults the SCI lists include:

  • Wall linings touching the floor decking or flooring board. It advises stopping wall plasterboard about 5 mm above the decking.
  • An external wall inner leaf or sheathing running continuously across a separating wall junction.
  • Internal walls that touch steel joists or break through a separating floor's ceiling.

The Approved Document also says fire stops in the cavity between frames must be flexible or fixed to only one frame, and that each layer of plasterboard should be fixed independently to the stud frame.

After a failure

Remedial treatment must suit the cause, and a failure raises questions over other rooms sharing the same separating element. The developer has to show those rooms meet the standard by more testing, by remedial work, or by showing the cause does not occur there.

After a failed set, the rate of testing should be increased until the building control body is satisfied the problem is solved.

Remedial work is judged by retest, because the building control body normally assesses its efficacy through additional sound insulation testing (paragraph 1.39).

Common questions

What are Robust Details?

Approved Document E says robust details have been accepted as an alternative to pre-completion testing in new houses and flats since 1 July 2004. They are high performance wall and floor constructions expected to be reliable without a test.

Who can carry out the tests?

The test report must give the testing organisation's third party accreditation number, for example UKAS or a European equivalent (paragraph 1.41).

Do internal partitions get tested?

The performance tables read here cover separating walls, floors and stairs. Confirm with the building control body whether any internal walls in a scheme are included.